How to calculate density at 15 °C

Updated 2 November 2026 · हिंदी में पढ़ें

Short answer

Read the hydrometer and the thermometer in the same sample at the same time. Look up the pair in ASTM Table 53B, with the reading across and the temperature down; where they meet is the density at 15 °C. Between printed figures, read in a straight line.

What you need

  • A clean, clear glass jar (the hydrometer jar).
  • A calibrated hydrometer for the range of your fuel. Petrol and diesel need different ones.
  • A calibrated thermometer.
  • Your company’s copy of Table 53B, the Table 53B look-up or the calculator.

The MDG makes it mandatory for a dealer to have calibrated hydrometers, thermometers and the ASTM density conversion table at the outlet.

Step by step

  1. Take the sample. From the nozzle in the morning, after letting a little fuel through; from each compartment’s manifold when a tanker arrives.
  2. Fill the jar and let air bubbles rise. Keep it out of the wind and direct sun.
  3. Lower the hydrometer gently. Let it float free, away from the jar’s wall. Give it a slight spin to break any surface film.
  4. Read the hydrometer at the level of the fuel’s flat surface, with your eye level with it. This is the observed density.
  5. Read the thermometer in the same jar straight away.
  6. Look it up. Reading across, temperature down.

Example 1: petrol

Hydrometer 741.0 kg/m³, temperature 26.5 °C.

Column 741, row 26.5 °C: 751.2 kg/m³ at 15 °C.

Example 2: diesel, between rows

Hydrometer 815.0 kg/m³, temperature 27.3 °C. The table is printed every 0.5 °C, so 27.3 falls between two rows. Read in a straight line between them, 27.3 being 0.6 of the way from 27.0 to 27.5. The answer is 823.7 kg/m³. The calculator does this step for you.

What to do with the answer

  • Morning: write it in the density register before sales start, by 10 AM at the latest.
  • Tanker: compare it with the invoice density. The difference must stay within ±3.0 kg/m³. See the density variation limit.
  • Check the range: BS-VI petrol is 720 to 775 kg/m³ and BS-VI diesel 810 to 845 kg/m³ at 15 °C. A figure outside is a reason to stop and check.

Figures here are for reference. Your oil company’s certified calibration chart, approved instruments and the Marketing Discipline Guidelines always prevail.

Questions

Can I just add or take off a fixed figure per degree?

Not safely. The change per degree depends on the density and is not quite constant. For petrol near 745 kg/m³ it is roughly 0.9 kg/m³ per degree; for diesel near 830 it is roughly 0.7. Use the table or the calculator.

How precise should the reading be?

Read the hydrometer to 0.5 kg/m³ and the thermometer to 0.5 °C. The table is printed to 0.1 kg/m³.

Sources

  1. BPCL, Marketing Discipline Guidelines 2024, clauses 1.2 and 1.4.1

Read next